Field titration kit for nitrite, used to check Cooltreat NCLT levels. Range 0–3400 ppm.
Measures nitrite levels in cooling water systems, range 0–3400 ppm. Designed to accompany Cooltreat NCLT.
Place a cold 0.5 mL sample in the test tube using the syringe provided, and add 2–3 mL of nitrite-free (e.g. deionised or drinking) water. Add 4 drops of reagent N1 — the sample turns orange. Add reagent N2M drop by drop until the colour shifts to pale blue; count the drops, each equal to 200 mg/L as nitrite (NO2).
Not applicable — this is a titration test kit.
Supplied as a complete field test kit.
This information is not to be taken as a warranty or representation for which Vecom Marine assumes legal responsibility. It is offered solely for your consideration, investigation and verification.