Field kit for DEHA (N,N-Diethylhydroxylamine), range 0–0.5 mg/L (0–500 ppb).
Measures oxygen/DEHA levels in boilers, range 0–0.5 mg/L (0–500 ppb), designed for use with Hydrazide.
Fill two cells with 10 mL of clean sample each; place one in the comparator as a blank. To the other, add 6 drops of DEHA Test Solution and mix, then add 1.0 mL (25 drops) of DEHA Indicator Solution and mix. Leave the cell in a dark area for 10 minutes, then rotate the comparator disc until the colour matches and record the reading. Testing in the light gives falsely high results; if the reading exceeds the highest standard, repeat on a diluted sample.
Not applicable — this is a colour-comparator test kit. Rated for roughly 65 uses.
Supplied as a complete field test kit (includes a DEHA disc, comparator, test cell, DEHA test solution and DEHA indicator solution).
This information is not to be taken as a warranty or representation for which Vecom Marine assumes legal responsibility. It is offered solely for your consideration, investigation and verification.